APC Smart-UPS RT 20KVA RM 230V SURT20KRMXLI
SKU
RTL880
Views: 4
Special Price ₦4,100,000 Regular Price ₦4,200,000
APC Smart-UPS RT 20kVA RM 230V SURT20KRMXLI
Output
-
Output power capacity16.0 KWatts / 20.0 kVA
-
Max Configurable Power (Watts)16.0 KWatts / 20.0 kVA
-
Nominal Output Voltage230V
-
Output Voltage NoteConfigurable for 400 or 415V 3 Phase nominal output voltage
-
Output Voltage DistortionLess than 5%
-
Output Frequency (sync to mains)50/60 Hz +/- 3 Hz user adjustable +/- 0.1
-
Other Output Voltages220, 240
-
Load Crest Factor3 : 1
-
TopologyDouble Conversion Online
-
Waveform typeSine wave
-
Overload Operation60 seconds @ 125% and 30 seconds @ 150%
-
Output Connections(2) IEC Jumpers (Battery Backup)(8) IEC 320 C19 (Battery Backup)(1) Hard Wire 3-wire (H N + G) (Battery Backup)
-
BypassBuilt-in Static Bypass, Internal Bypass (Automatic and Manual), Optional External Bypass
Input
-
Nominal Input Voltage230V , 400V 3PH
-
Input frequency40 - 70 Hz (auto sensing)
-
Input ConnectionsHard Wire 3 wire (1PH+N+G), Hard Wire 5-wire (3PH + N + G)
-
Input voltage range for main operations160 - 280V
-
Input Total Harmonic DistortionLess than 5% for full load
-
Other Input Voltages220, 240
-
Maximum Input Current115.0A
-
Input Power Factor at Full Load0.98
Batteries & Runtime
-
Battery typeMaintenance-free sealed Lead-Acid battery with suspended electrolyte : leakproof
-
Included Battery Modules4
-
Typical recharge time2.5hour(s)
-
Nominal Battery Voltage+/-192 V (split battery referenced to neutral)
-
Replacement BatteryAPCRBC140
-
Expected Battery Life (years)3 - 5
-
RBC Quantity4
-
Extendable Run Time1
-
Extended Run OptionsAPC-Smart-UPS-RT-20kVA-RM-230V
-
End of Discharge Battery Voltage+/-154 V
-
Efficiency in Battery Operation93.0 %
-
RuntimeView Runtime GraphView Runtime Chart
-
EfficiencyView Efficiency Graph
Communications & Management
-
Interface Port(s)DB-9 RS-232 , RJ-45 10/100 Base-T , Smart-Slot
-
Pre-Installed SmartSlot™ CardsAP9631
-
Control panelMulti-function LCD status and control console
-
Audible AlarmAudible and visible alarms : configurable delays
-
Emergency Power Off (EPO)Yes
Surge Protection and Filtering
-
FilteringFull time multi-pole noise filtering : 0.3% IEEE surge let-through : zero clamping response time : meets UL 1449
Physical
-
Maximum Height533mm , 53.3CM
-
Maximum Width432mm , 43.2CM
-
Maximum Depth773mm , 77.3CM
-
Rack Height12U
-
Net Weight247.73KG
-
Shipping weight314.09KG
-
Shipping Height990mm , 99.0CM
-
Shipping Width610mm , 61.0CM
-
Shipping Depth1003mm , 100.3CM
-
ColorBlack
-
Units per Pallet1.0
Environmental
-
Operating Temperature0 - 40 °C
-
Operating Relative Humidity0 - 95 (non-condensing) %
-
Operating Elevation0-3000meters
-
Storage Temperature-15 - 45 °C
-
Storage Relative Humidity0 - 95 (non-condensing) %
-
Storage Elevation0-15000meters
-
Audible noise at 1 meter from surface of unit59.0dBA
-
Online thermal dissipation3770.0BTU/hr
-
Protection ClassIP 20
Conformance
Write Your Own Review