Huawei UPS2000-G series (15-20kVA)
UPS2000-G-15K is used for power systems in various scenarios, including communications rooms, customer service centers, laboratories, instrument rooms, control rooms, offices, billing centers, precision control rooms, and process control centers. UPS2000-G-15K is an online double conversion and sine wave power system that delivers continuous, high-quality AC power to precision instruments. The UPS can be tower- or rack-mounted, depending on the site requirements. It supplies AC power to small computer centers, networks, communications systems, automatic control systems, and precision instruments. The UPS provides optional components, such as a power distribution unit (PDU), monitoring ports, and an SNMP card, to deliver comprehensive solutions for low- and medium-powered equipment.
Product Features
Reliable
- 5 kA lightning protection design, to reduce lightning related failure rate
- Wide input voltage range to minimize battery use: 280-176 Vac for 100% load; 176-80 Vac for 100%-40% load (derating linearly)
- Alarms for key components including bus capacitance, fans, and batteries in advance to eliminate potentials failures
- High overload capacity: 125% overload for 5min and 150% overload for 1min
Efficient
- High on-line efficiency: up to 95% for 15/20 kVA; 94.5% for 10 kVA and 93.5% for 6 kVA; the global first batch of UPSs achieving “Energy star” certificate
- Be conformed with EU Environment certification ROSH&Reach
- High input power factor: > 0.99, saving the investment of input power distribution
- ECO mode that can be enabled in good grid areas to cut energy loss more efficiently
Convenient
- High expandability: 4 UPSs maximally in a parallel system
- Adjustable battery number: 16-20 for 6/10 kVA and 32-40 for 15/20kVA
- Rack/tower convertible
- Friendly interface in LCD, supports several languages and can be rotated according to installation type
- Hierarchical power-off in single UPS mode to extend the backup time for important loads
Intelligent
- Various communication modes including RS485, SNMP, USB, and dry contact
- Only one communication card needed to manage all the UPSs in a parallel system
- Intelligent charging and discharging management, temperature compensation, and intelligent hibernation technology, prolonging the battery life by 50%
- Black box that records operation data to facilitate fault locating and clearing
Product Specification
Capacity |
15kVA/13.5kW |
20kVA/18kW |
Model |
UPS2000-G-15KRTL |
UPS2000-G-20KRTL |
Input |
||
Input and output formats |
1 ph input /1 ph output |
|
Rated Voltage |
L-N: 220/230/240Vac |
|
Input Voltage Range |
L-N: 80-280Vac |
|
Input Frequency Range |
40-70Hz |
|
Battery Voltage |
±(192-240)Vdc |
|
Output |
||
Output Voltage |
L-N: 220/230/240Vac |
|
Output Frequency |
Tracking bypass input (Online mode); 50/60±0.1 Hz(Battery Mode) |
|
Waveform |
Sine wave; THDv<2% |
|
Output port |
OT connect terminal |
|
System Efficiency |
Up to 95% |
|
Overload Capacity |
125% overload for 5 min; 150% overload for 1 min |
|
Environment |
||
Operating Temperature |
0℃-40℃ |
|
Storage Temperature |
-40℃-70℃ |
|
Relative Humidity |
0%-95%(No condensing) |
|
Operating Altitude |
1000m |
|
Audible Noise |
<58dB |
|
Others |
||
Height×Width×Depth (mm) |
130×430×685 |
|
Weight |
32kg |
|
Communication interfaces |
RS485、USB、SNMP、dry contacts |
|
Certification |
CB、CE、TLC、CQC、ECA |
For more details, please refer to Huawei Small UPS UPS2000-G Series (1-20kVA) Datasheet (PDF).
Configuration
UPS
UPS2000-G-15KRTL |
15kVA/13.5kW,support 1-phase input / 1-phase output , 3-phase input / 1-phase output and 3-phase input / 3-phase output |
UPS2000-G-20KRTL |
20kVA/18kW,support 1-phase input / 1-phase output , 3-phase input / 1-phase output and 3-phase input / 3-phase output |
Battery
Battery pack |
240V/7Ah battery pack |
Optional components
Communication card |
|
Dry Contact Card |
provides six alarm dry contact outputs and two dry |
Modbus Card |
Provides an RS485 networking solution for remote UPS management. |
SNMP Card |
Remotely manage the UPS by |
Power Distribution Component |
|
PDU |
Supports 2 units parallel system, protects AC input and output, increases output sockets, and implements online UPS maintenance |
STS(16A) |
switching primary loads between two power sources |
Others |
|
Temperature Sensor |
monitoring the temperatures of the battery packs or between batteries |
Ambient Temperature and Humidity Sensor |
working with the SNMP card and testing the temperature and humidity of UPS |
Rails |
configuring with rack |