Blue Gate 6KVA/4.2KW Online UPS
SKU
RTLIS-000393-1
Views: 7
Special Price ₦1,550,000 Regular Price ₦1,650,000
- For office network, servers & other IT equipment
- High frequency & double conversion online technology
- Fully digitized microprocessor control
- Wide input voltage range
- LCD display
- UPS start up without battery; Cold start
- Advanced battery management
- Lightning & surge protection
- Short circuit & overload protection
- Fan speed auto control when loads varies
- Network/fax/modem surge protection
- Optional extension battery pack
- Battery voltage display
- Load capacity display
- EMI/RFI noise filter
- Smart RS232 communication with monitoring software
- Optional SNMP card slot
- EPO function (optional)
- Good for IT equipment: network, servers etc
- High frequency and double conversion online technology
- Fully digitized microprocessor control
- Wide input voltage range
- LCD display
- UPS start up without battery; Cold start
- Advanced battery management
- Automatic battery charging in UPS off mode
- Lightning and surge protection
- Short circuit and overload protection
- Fan speed auto control when loads varies
- Network/fax/modem surge protection
- Optional extension battery pack
- Battery voltage display
- Load capacity display
- EMI/RFI noise filter
- Smart RS232 communication with monitoring software
Blue Gate 6kVA Online UPS
Capacity
|
6KVA/4.2KW
|
|
|
INPUT
|
|
Voltage Range
|
176±5VAC - 276±5VAC
176±5VAC - 276±5VAC |
Frequency Range Phase
|
46 - 54Hz±0.5Hz or 56 - 64Hz±0.5Hz auto sensing
|
Power Factor
|
≥0.98
|
OUTPUT
|
|
Voltage Range Phase
|
220Vac±1%
|
Frequency Range
|
Synchronise with the utility on AC mode; 50Hz/60Hz±0.2% on battery mode
|
THD(linear load)
|
3%
|
THD(non-linear load)
|
6%
|
Load capability
|
>110%, 30s turn to bypass mode; >150%, 300ms turn to bypass mode
|
Crest Factor
|
03:01:00
|
Short circuit protection
|
5 cycles turn off inverter, no transfer to bypass, provide alarm (AC mode).
|
Waveform
|
Pure sine wave
|
Transfer Time
|
0ms (Between AC mode and Battery mode)
0ms (Between AC mode and Battery mode) |
Efficiency
|
≥88%
|
Model of Battery
|
12V sealed VRLA maintenance free
|
DC Voltage
|
240VDC
|
Battery
|
20x12V/7AH
|
Back up time(half load)
|
20min
|
Back up time(full load)
|
7min
|
Charge current(standard unit)
|
1A
|
Charge current(long time unit)
|
5A
|
Recharge time
|
90 % capacity after 8hrs charging
|
Communication Interface
|
RS232; SNMP (optional)
|
Parallel port
|
parallel availability for redundancy and load sharing up to three units
|
LCD Indicator
|
1. input voltage/frequency, battery voltage, output voltage/frequency, load watt/VA and percent, inverter temperature
2.Operation mode such as "on line", "on batt", or " or bypass" |
LED Indicator
|
1. Green LED for normal operation,
2. Yellow LED for warning condition, 3.Red LED for abnormal operation |
Noise Level
|
<55dB>
|
Temperature of the Environment
|
0⁰C - 40⁰C
|
Humidity of the Environment
|
0% - 95%(non-condensing)
|
Altitude of the Environment
|
<1500m>
|
Storage temperature
|
−40⁰C - 50⁰C
|
Standard unit Net/Gross weight (kg)
|
89/104
|
Long time unit Net/Gross weight (kg)
|
34/48
|
Dimension (W*D*H)mm
|
270x570x720
|
Packing Dimension (W*D*H)mm
|
370x670x940
|